Vortex Wafer / Flanged Insertion Model

Vortex Wafer / Flanged Insertion Model
Vortex Wafer / Flanged Insertion Model
Vortex Wafer / Flanged Insertion Model

Home > Products > Flow > Vortex In line Flow Meters > Vortex Wafer / Flanged Insertion Model

Vortex Wafer / Flanged Insertion Model

Specification

    • Velocity Ranges: Liquid -1.32 to 32ft/ sec
      Gas & Stream -0.33 to 250ft/ sec
    • Accuracy: ±0.5% of rate
    • Repeatability: ±0.25% of rate
    • Pressure: Maximum 103 barg or flange rating
    • Process Temperature: -70 to 232ºC std optional max 316ºC
    • Transducer Input Power: 15 to 30 VDC / 115 to 230 VAC optional
    • Transducer Output: 4-20 mA or 5V TTL pulse output
    • Linear Range: Renolds number 710000
    • Materials of Construction: All stainless steel
    • Electronics Housing: Epoxy coated aluminium
    • Enclosure Protection: NEMA 4x / IP66
    • Process Connections: ANSI 150 RF, 300, 600, wafer

Options

    • Calibrations: All other gas calibrations available
    • Remote Electronics: Available options
    • Hot Tap Facility: Package available

 

Acrobat File VX Flowmeter.pdf
Filesize: 629K

PDF files require Adobe Acrobat Reader. Click here to download it.

Search Products

OK

Email Newsletter Signup

Enter your email address below to receive regular news and product updates from us.

OK
You may be assured that the personal information you provide to Cache is treated with utmost care to ensure safety, security & confidentiality. Cache does not provide customer identifiable information to third parties.

Require Assistance?

Cache Instrumentation


We Can Help...Click Here

Copyright ©2007 Cache Instrumentation Ltd, All rights reserved. Terms & Conditions

Contact Cache Instrumentation, UK for Pressure Transmitters, Temperature Sensors and More Cache Instrumentation, Wakefield, West Yorkshire, UK • Web Site Designed and produced by Hayes Design and Media - Tel: 07900 277889